| 2001-01-08 00:00:00 | JOB SPEC.15400-PART 1-REVISE STANDARD TO |
| | READ NFPA 54,NOT NFPA 56. |
| | |
| | SPEC.15400-PART 2-FITTINGS NOT PERMITTED |
| | ON WATER DISTRIBUTION LINES UNDER BLDG. |
| | SLAB PER COUNTYWIDE AMENDMENTS TO SPC |
| | 611.3. |
| | |
| | SUBMIT MANUF.SHEETS FOR WATER SOFTENER |
| | PER SPC SEC.615. |
| | |
| | CITY OF WPB UTILITIES SHALL APPROVE SIZE |
| | AND DESIGN OF GREASE TRAP.SUBMIT |
| | APPROVAL FORM FROM UTILITIES.CONTACT |
| | R.COMPO AT (561)835-7423. |
| | |
| | PLBG.FIXTURES IN ISOLATION ROOM SHALL BE |
| | FULLY ACCESSIBLE PER FACBC SEC.4.1.3(11) |
| | TOILET IN PRESIDENT'S OFFICE SHALL BE |
| | ADAPTABLE. |
| | |
| | SINK IN TEACHER'S LOUNGE SHALL COMPLY W/ |
| | FACBC SEC.4.24.1-4.24.7.CLEARLY SHOW |
| | ON PLANS. |
| | |
| | CLEARLY SHOW HEIGHT OF H.C. URINAL ON |
| | PLANS.COMPLY W/FACBC SEC.4.18.2. |
| | |
| | SUBMIT A COMPLETE ISOMETRIC FOR THE |
| | ENTIRE STORM WATER SYSTEM.SHOW ALL PIPE |
| | SIZES AND SQUARE FOOTAGE DRAINED BY EACH |
| | ROOF DRAIN PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1.,SPC SEC.1108. |
| | |
| | AN ADDITIONAL STALL COMPLYING W/FACBC |
| | SEC.4.22.4.SHALL BE PROVIDED IN THE |
| | WOMEN'S TOILET ROOM. |
| | |
| | A TWO WAY CLEANOUT BROUGHT TO GRADE |
| | SHALL BE INSTALLED IN THE INLET AND |
| | OUTLET OF THE GREASE INTERCEPTOR PER |
| | SPC SEC.1004.8, |
| | |
| | THE CURRENT C.O.'S SHALL BE RELOCATED TO |
| | COMPLY W/SPC SEC.307.5. |
| | |
| | THE DISTANCE BETWEEN SAN.AND WATER SHALL |
| | COMPLY W/SPC SEC.608.3(SHT.P-1) |
| | |
| | SUBMIT SANITARY ISOMETRIC FOR REVEW.THE |
| | DRAWING ON THE PLANS HAS TOO MANY |
| | VIOLATIONS TO LIST.COUNTYWIDE AMENDMENT |
| | TO SPC SEC.104.2.1`. |
| | |
| | SIZE THE WATER RISER IN ITS ENTIRETY. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | SEC.610.4.1.,610.4.4 |
| | |
| | |
| | |
| | |
| | |
| | YOU MUST COMPLETE A WAIVER FOR THE USE |
| | OF CHILREN'S FIXTURES IN THE SCHOOL.THE |
| | ACCESSIBILITY STANDARD IS ONLY A GUIDE - |
| | LINE AND HAS NOT BEEN ADOPTED BY THE |
| | DEPT.OF JUSTICE.THE WAIVER SHALL BE |
| | SUBMITTED TO STATE OF FL.DEPT.OF COMM. |
| | AFFAIRS. |
| | |
| | THE TOILET STALLS IN THE GYM SHALL CON- |
| | TAIN AN ACCESIBLE LAV.WITHIN THE STALLS |
| | PER FACBC SEC.4.17.3. |
| | |
| | SHOWERS IN GYM SHALL COMPLY W/FACBC |
| | 4.21.2.FOR SIZE AND CLEARANCE.SEE SECS. |
| | 4.21.3- 4.21.7. |
| | |
| | ALL PUBLIC AND COMMON AREA TOILET ROOMS |
| | SHALL COMPLY W/FACBC SEC.4.1.3(11),4.22. |
| | |
| | THE BUILDING PLANS SHALL BEAR THE STAMP |
| | FROM THE HEALTH DEPT.,NOT JUST THE CIVIL |
| | DWGS.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 101.4.7. |