Plan Review Notes
Plan Review Notes For Permit 99080492
Permit Number 99080492
Review Stop M
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1) FIRE DAMPERS REQUIRED AT ALL DUCT
 PENETRATIONS OF RATED WALLS. PROVIDE
 SPECIFIC LOCATION AND INSTALLATION
 DETAILS AS PER 1997 SMC 610.6
 2) EXHAUST FAN NUMBERS ON SCHEDULE DO
 NOT CORRESPOND TO EXHAUST FANS SHOWN ON
 PLAN. PROVIDE REVISED PLANS SHOWING
 CLARIFICATION OF EXHAUST FAN INFORMATION
 IF THIS REQUIRES A CHANGE OF THE AIR
 BALANCE SCHEDULE PROVIDE REVISED
 SCHEDULE
 3) EQUIPMENT SERVING AREAS USED FOR
 EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT
 SMOKE DETECTOR REGARDLESS OF SIZE OF
 EQUIPMENT PER 1997 SMC 406.2
 4) ADDITIONAL PERMITS REQUIRED FOR
 KITCHEN HOOD, SUPPRESSION SYSTEMAND
 WALK IN COOLERS/FREEZERS SUBMIT DETAILED
 PLANS AT TIME OF MECHANICAL PERMIT APP-
 LICATION FOR THESE SYSTEMS
 5) THE ABOVE CLARIFICATIONS EXCEPT ITEM
 4 SHALL BE SUBMITTED FOR PLAN REVIEW
 PRIOR TO ANY MECHANICAL WORK BEING DONE
 ON THIS PROJECT