| Plan Review Notes For Permit 99080492 |
| Permit Number |
99080492 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) FIRE DAMPERS REQUIRED AT ALL DUCT | | | PENETRATIONS OF RATED WALLS. PROVIDE | | | SPECIFIC LOCATION AND INSTALLATION | | | DETAILS AS PER 1997 SMC 610.6 | | | 2) EXHAUST FAN NUMBERS ON SCHEDULE DO | | | NOT CORRESPOND TO EXHAUST FANS SHOWN ON | | | PLAN. PROVIDE REVISED PLANS SHOWING | | | CLARIFICATION OF EXHAUST FAN INFORMATION | | | IF THIS REQUIRES A CHANGE OF THE AIR | | | BALANCE SCHEDULE PROVIDE REVISED | | | SCHEDULE | | | 3) EQUIPMENT SERVING AREAS USED FOR | | | EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT | | | SMOKE DETECTOR REGARDLESS OF SIZE OF | | | EQUIPMENT PER 1997 SMC 406.2 | | | 4) ADDITIONAL PERMITS REQUIRED FOR | | | KITCHEN HOOD, SUPPRESSION SYSTEMAND | | | WALK IN COOLERS/FREEZERS SUBMIT DETAILED | | | PLANS AT TIME OF MECHANICAL PERMIT APP- | | | LICATION FOR THESE SYSTEMS | | | 5) THE ABOVE CLARIFICATIONS EXCEPT ITEM | | | 4 SHALL BE SUBMITTED FOR PLAN REVIEW | | | PRIOR TO ANY MECHANICAL WORK BEING DONE | | | ON THIS PROJECT |
|