| Plan Review Notes For Permit 99080492 |
| Permit Number |
99080492 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* PROVISO ***************** | | | | | | 1)NOTE: LOCAL CODE FOR OUTLET SPACING. | | | | | | 2)NOTE: MISSING OUTLET FOR MECH ROOM | | | ART 210-63 | | | | | | 3)NOTE:ALL BATH REC TO BE GFI 210-8-B | | | | | | 4)NOTE: ROOMS SHOWN AS STORAGE WITH | | | ELEC. PANELS?? SEE 240-24-D AND 384-7 | | | PLEASE CHECK YOUR LOACTIONS | | | | | | PLEASE SUBMIT THE REVISED SHEETS FOR | | | REVIEW BEFORE ROUGH ELECTRICAL IS CALLED | | | IN. IF THERE ARE ANY QUESTIONS PLEASE | | | CALL 659-8096 EXT 8372 |
|