| 2001-01-08 00:00:00 | CIVIL DRAWINGS SHALL BE SIGNED AND |
| | SEALED BY PROFESSIONAL OF RECORD PER F.S |
| | 471.025. |
| | |
| | SHOW LOCATION AND SIZE OF GREASE TRAP |
| | ON PLANS.MIN.SIZE SHALL BE 750 GALS. |
| | CONTACT RODNEY COMPO/CITY OF WPB |
| | REGIONAL SEWER TREATMENT PLANT FOR |
| | SIZING REQS.AT (561)835-7423.(GREASE |
| | TRAP CANNOT BE LOCATED IN FOOD PREP AREA |
| | |
| | SUBMIT RISER DIAGRAM FOR STORM DRAINAGE |
| | SYSTEM AND SHOW PROVISIONS FOR SECONDARY |
| | DRAINAGE.COMPLY W/CHAPT.11 OF SPC. |
| | |
| | SUBMIT SANITARY AND WATER RISERS THAT |
| | COMPLY FULLY TO THE SPC IN ALL RESPECTS. |
| | |
| | SINK IN TEACHER'S LOUNGE SHALL COMPLY |
| | W/FACBC SEC.4.24.1-4.24.7. |
| | |
| | EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY W/FACBC SEC.4.1.3.(11), |
| | 4.22. |
| | |
| | WATER CLOSETS IN H.C.STALLS SHALL BE |
| | LOCATED IN THE CORNER,DIAGONAL TO THE |
| | DOOR.FACBC SEC.4.17.3. |
| | |
| | CLEARLY SHOW DISTANCE BETWEEN THE WATER |
| | SERVICE AND THE BUILDING SEWER.COMPLY |
| | W/SPC 608.3. |
| | |
| | SHOWERS IN GYM SHALL COMPLY W/FACBC |
| | SEC.4.21.1-4.21.7. |
| | |
| | GYM RESTROOMS SHALL BE EQUIPPED W/FULLY |
| | ACCESSIBLE STALLS PER FACBC SECS.4.1.3 |
| | (11),4.22., |
| | |
| | SUBMIT OCCUPANT LOAD OF GYM.TYPE AND |
| | AMOUNT OF REQD.PLBG.FIXTURES SHALL |
| | COMPLY W/TABLE 407 OF SPC. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC SEC.501.7(A).A PERMANENT LADDER |
| | SHALL BE INSTALLED OR HEATER SHALL BE |
| | LOCATED ON FLOOR. |
| | |
| | PLANS SHALL BE ROUTED TO PALM BEACH |
| | COUNTY HEALTH FOR REVIEW AND APPROVAL |
| | PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 101.4.7. |
| | |
| | SHT.A-3-SHOW INSIDE CLEAR DIMENSIONS |
| | (LXW)OF TOILET ROOMS AND STALLS.COMPLY |
| | W/FACBC SEC.4.16.2,4.17.3. |