Plan Review Notes
Plan Review Notes For Permit 99080492
Permit Number 99080492
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CIVIL DRAWINGS SHALL BE SIGNED AND
 SEALED BY PROFESSIONAL OF RECORD PER F.S
 471.025.
  
 SHOW LOCATION AND SIZE OF GREASE TRAP
 ON PLANS.MIN.SIZE SHALL BE 750 GALS.
 CONTACT RODNEY COMPO/CITY OF WPB
 REGIONAL SEWER TREATMENT PLANT FOR
 SIZING REQS.AT (561)835-7423.(GREASE
 TRAP CANNOT BE LOCATED IN FOOD PREP AREA
  
 SUBMIT RISER DIAGRAM FOR STORM DRAINAGE
 SYSTEM AND SHOW PROVISIONS FOR SECONDARY
 DRAINAGE.COMPLY W/CHAPT.11 OF SPC.
  
 SUBMIT SANITARY AND WATER RISERS THAT
 COMPLY FULLY TO THE SPC IN ALL RESPECTS.
  
 SINK IN TEACHER'S LOUNGE SHALL COMPLY
 W/FACBC SEC.4.24.1-4.24.7.
  
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY W/FACBC SEC.4.1.3.(11),
 4.22.
  
 WATER CLOSETS IN H.C.STALLS SHALL BE
 LOCATED IN THE CORNER,DIAGONAL TO THE
 DOOR.FACBC SEC.4.17.3.
  
 CLEARLY SHOW DISTANCE BETWEEN THE WATER
 SERVICE AND THE BUILDING SEWER.COMPLY
 W/SPC 608.3.
  
 SHOWERS IN GYM SHALL COMPLY W/FACBC
 SEC.4.21.1-4.21.7.
  
 GYM RESTROOMS SHALL BE EQUIPPED W/FULLY
 ACCESSIBLE STALLS PER FACBC SECS.4.1.3
 (11),4.22.,
  
 SUBMIT OCCUPANT LOAD OF GYM.TYPE AND
 AMOUNT OF REQD.PLBG.FIXTURES SHALL
 COMPLY W/TABLE 407 OF SPC.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7(A).A PERMANENT LADDER
 SHALL BE INSTALLED OR HEATER SHALL BE
 LOCATED ON FLOOR.
  
 PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH FOR REVIEW AND APPROVAL
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 SHT.A-3-SHOW INSIDE CLEAR DIMENSIONS
 (LXW)OF TOILET ROOMS AND STALLS.COMPLY
 W/FACBC SEC.4.16.2,4.17.3.