| 2001-01-08 00:00:00 | **REVISION 3 ACCEPTED W/ PROVISO******** | | | PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | PROVIDE AIR BALANCE CALCULATIONS PER | | | 1997 SMC 501.2 | | | 1997 SMC DOES NOT ALLOW THE USE OF | | | PUBLIC EXIT CORRIDORS FOR PLENUMS FOR | | | ADJOINING AREAS 609.1.1 | | | EF 2A SHOWS AS RESTROOM EXHAUST ON | | | SCHEDULE BUT IS IN CORRIDOR ON PLAN | | | DEFINE USE/LOCATION | | | AHU IN CORRIDOR SHOW NO RETURN AIR. IS | | | THIS 100% OUTSIDE AIR? SEE AHU 8 AND 16 |
|