Plan Review Notes
Plan Review Notes For Permit 99080492
Permit Number 99080492
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**REVISION 3 ACCEPTED W/ PROVISO********
 PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 PROVIDE AIR BALANCE CALCULATIONS PER
 1997 SMC 501.2
 1997 SMC DOES NOT ALLOW THE USE OF
 PUBLIC EXIT CORRIDORS FOR PLENUMS FOR
 ADJOINING AREAS 609.1.1
 EF 2A SHOWS AS RESTROOM EXHAUST ON
 SCHEDULE BUT IS IN CORRIDOR ON PLAN
 DEFINE USE/LOCATION
 AHU IN CORRIDOR SHOW NO RETURN AIR. IS
 THIS 100% OUTSIDE AIR? SEE AHU 8 AND 16