| Plan Review Notes For Permit 99080492 |
| Permit Number |
99080492 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************UNSAT***************** | | | | | | SAME AS ORIGINAL NOTES | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT!! TO INCLUDE PANELS. AS PER | | | ARTS:230-65/110-9/215-5 | | | | | | 2)NOTE: PLEASE CHECK GROUNDING ELECTRODE | | | CONDUCOTR SIZE AS PER TABLE 250-94 | | | EXCEPT. #2 SUM OF SERVICE CONDUCTORS. | | | | | | 3)NOTE: PLEASE SHOW BLDG.STEEL AS PART | | | OF THE GOUNDING SYSTEM AS PER 250-81/ | | | 215-5 | | | | | | PLANS WOULD HAVE PASSED AS PROVISO BUT | | | WERE COMING BACK TO YOU FOR PLUMB/MECH. | | | PLEASE DRAW UP NEW FULL SIZE E-4 FOR | | | LARGE SET WITH THE INFORMATION ABOVE | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 561-659-8096 | | | EXT.8372 |
|