| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT SITE PLAN SHOWING WATER AND SEWER |
| | LINES TO THE STRUCTURES.SPC 104.2.1. |
| | |
| | DRINKING FOUNTAINS SHALL BE REQUIRED AT |
| | RATIO OF 1 PER 3 CLASSROOMS & NOT LESS |
| | THAN 1 PER FLOOR.SPC TABLE 407. |
| | |
| | SHOW LOCATION AND SIZE OF GREASE TRAP. |
| | SUBMIT DETAIL OF GREASE TRAP.CONTACT |
| | RODNEY COMPO /CITY OF WPB REGIONAL SEWER |
| | TREATMENT PLANT FOR SIZE REQS.AT |
| | (561)835-7423.(GREASE TRAP CANNOT BE |
| | LOCATED IN FOOD PREP AREA.) |
| | |
| | SUBMIT ISOMETRIC DRAWINGS FOR ALL STORM, |
| | SANITARY AND WATER SYSTEMS.SPC 104.2.1. |
| | |
| | SUBMIT DETAILS AND U.L.ASSEMBLY NUMBER |
| | FOR FIRE SAFING OF PIPE PENETRATIONS |
| | THROUGH RATED WALLS PER SPC 104.2.4. |
| | |
| | SINK IN TEACHER'S LOUNGE SHALL COMPLY W/ |
| | FACBC SECS.4.24.1-4.24.7. |
| | |
| | EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY W/FACBC SEC.4.1.3(11),4.22. |
| | |
| | WATER CLOSETS IN H.C.STALLS SHALL BE |
| | LOCATED IN THE CORNER,DIAGONAL TO THE |
| | DOOR.FACBC SEC.4.17.3. |
| | |
| | NUMBER OF REQD.URINALS SHALL COMPLY W/ |
| | SPC TABLE 407,FOOTNOTE #3.(3 REQD.) |
| | |
| | FLOOR DRAINS AND WAINSCOTING ARE REQ'D. |
| | IN ALL TOILET ROOMS PER SBC SEC.1204.2. |
| | |
| | SUBMIT ELEVATION DETAILS FOR ALL |
| | HANDICAP FIXTURES.COMPLY W/FACBC. |
| | |
| | SHEETS P-1 & P-2 SHALL BE SIGNED AND |
| | SEALED BY DESIGN PROFESSIONAL PER SPC |
| | SEC.104.2.3. |
| | |
| | DISTANCE BETWEEN WATER SERVICE AND BLDG. |
| | SEWER SHALL COMPLY W/SPC SEC.608.3. |
| | |
| | PLBG.FIXTURES IN GYM SHALL COMPLY W/ |
| | FACBC SEC.4.1.3(11),4.22. |
| | |
| | SUBMIT OCCUPANT LOAD OF GYM.NUMBER OF |
| | REQD.FIXTURES SHALL COMPLY W/TABLE 407 |
| | OF SPC. |
| | |
| | SHT P-2-DETAIL 3A-FLOOR SINKS EXCEED |
| | DISTANCE FROM VENT PER TABLE 908.1 AND |
| | ARE NOT PROPERLY VENTED. |
| | |
| | SHT.P-2.DETAIL#4-LOCATION OF LAVATORY |
| | DOESN'T CORRELATE W/SHT.A-1.COMPLY W/ |
| | FACBC SEC.4.17.3. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC 501.7.A PERMANENT LADDER SHALL |
| | BE INSTALLED OR HEATER SHALL BE LOCATED |
| | ON FLOOR. |
| | |
| | SUBMIT COMPLETE PLANS FOR ANY GAS WORK |
| | BEING PERFORMED IF APPLICABLE.STD.GAS |
| | CODE SEC.302. |
| | |
| | PLANS SHALL BE ROUTED TO HEALTH DEPT.FOR |
| | REVIEW AND APPROVAL PER SPC 101.4.7. |