| 2001-01-08 00:00:00 | ****REVISION 3 ACCEPTED W/ PROVISO****** |
| | |
| | 1)ASHRAE 62-89 6.1.3.4 ALLOWS FOR REDUC- |
| | TION OF OUTDOOR AIR ONLY WHEN PEAK OCCUP |
| | ANCIES OCCUR FOR LESS THAN 3 HOURS DURA- |
| | TION AND NOT LESS 1/2 THE MAX. IS USED |
| | FOR THE AVERAGE. THIS DOES NOT FIT THAT |
| | CRITERIA. |
| | 2)ASHRAE 62-89 6.1.3.2 ALLOWS REDUCTION |
| | OF OUTSIDE AIR BELOW TABLE 2 AMOUNTS |
| | USING PROCEDURE 6.2 PROVIDE CALCULATIONS |
| | ON BASIS FOR EQUIPMENT DETERMINATION AND |
| | AIR SYSTEM CLEANING EFFICIENCY PER |
| | SECTION 6.2 |
| | 3) RE: ITEM NO. 2 AIR BALANCE, SCHEDULE |
| | REQUESTED ON AIR BALANCE TO ASSURE COMP- |
| | LIENCE WITH 1994 SMC 501.2 SHOW TOTAL |
| | OUTSIDE AIR SUPPLIED, TOTAL EXHAUST AIR |
| | AND EXFILTRATION QUANTITIES. |
| | 4)KITCHEN/DINING ROOM REQUIRES 20 CFM |
| | PER PERSON,NOT 15 CFM PER PERSON. |
| | 5)REDUCTION RATE ACCEPTABLE FOR DINING |
| | ROOM AND AUDITORIUM IF PEAK OCCUPANCY IS |
| | LESS THAN 3 HOURS AND AVERAGE OCCUPANCY |
| | USED IS NOT LESS THAN 1/2 THE MAXIMUM. |
| | 6) ITEM NO. 3 RE: DUCT SMOKE DETECTORS, |
| | THE DOCUMENT RECEIVED BY THE BUILDING |
| | DIVISION IS A COPY AND THERE IS NO |
| | "MECHANICAL LEGEND" ON SCALED PLAN AND |
| | THE SYMBOLS ON PLANS RECEIVED ARE UNREAD |
| | ABLE DO TO COPY QUAILITY |
| | 7) AIR HANDLERS PROVIDING AIR FOR AREAS |
| | USED FOR EXITS OR EXIT ACCESS CORRIDORS |
| | SHALL HAVE AUTOMATIC SHUT DOWN PER 1994 |
| | SMC 406.2 |
| | 8) PLAN DOCUMENTS RECEIVED ARE NOT |
| | ORIGINAL SIGNED AND SEALED DOCUMENTS AND |
| | ARE NOT ACCEPTABLE AS SUBMITTED. PROVIDE |
| | ORIGINAL, LEGABLE DOCUMENTS, SIGNED AND |
| | SEALED BY STATE OF FLORIDA LICENSED ENG- |
| | INEER 104.2.3 CITY AMENDMENTS |