Date Text
2001-01-08 00:00:00****REVISION 3 ACCEPTED W/ PROVISO******
  
 1)ASHRAE 62-89 6.1.3.4 ALLOWS FOR REDUC-
 TION OF OUTDOOR AIR ONLY WHEN PEAK OCCUP
 ANCIES OCCUR FOR LESS THAN 3 HOURS DURA-
 TION AND NOT LESS 1/2 THE MAX. IS USED
 FOR THE AVERAGE. THIS DOES NOT FIT THAT
 CRITERIA.
 2)ASHRAE 62-89 6.1.3.2 ALLOWS REDUCTION
 OF OUTSIDE AIR BELOW TABLE 2 AMOUNTS
 USING PROCEDURE 6.2 PROVIDE CALCULATIONS
 ON BASIS FOR EQUIPMENT DETERMINATION AND
 AIR SYSTEM CLEANING EFFICIENCY PER
 SECTION 6.2
 3) RE: ITEM NO. 2 AIR BALANCE, SCHEDULE
 REQUESTED ON AIR BALANCE TO ASSURE COMP-
 LIENCE WITH 1994 SMC 501.2 SHOW TOTAL
 OUTSIDE AIR SUPPLIED, TOTAL EXHAUST AIR
 AND EXFILTRATION QUANTITIES.
 4)KITCHEN/DINING ROOM REQUIRES 20 CFM
 PER PERSON,NOT 15 CFM PER PERSON.
 5)REDUCTION RATE ACCEPTABLE FOR DINING
 ROOM AND AUDITORIUM IF PEAK OCCUPANCY IS
 LESS THAN 3 HOURS AND AVERAGE OCCUPANCY
 USED IS NOT LESS THAN 1/2 THE MAXIMUM.
 6) ITEM NO. 3 RE: DUCT SMOKE DETECTORS,
 THE DOCUMENT RECEIVED BY THE BUILDING
 DIVISION IS A COPY AND THERE IS NO
 "MECHANICAL LEGEND" ON SCALED PLAN AND
 THE SYMBOLS ON PLANS RECEIVED ARE UNREAD
 ABLE DO TO COPY QUAILITY
 7) AIR HANDLERS PROVIDING AIR FOR AREAS
 USED FOR EXITS OR EXIT ACCESS CORRIDORS
 SHALL HAVE AUTOMATIC SHUT DOWN PER 1994
 SMC 406.2
 8) PLAN DOCUMENTS RECEIVED ARE NOT
 ORIGINAL SIGNED AND SEALED DOCUMENTS AND
 ARE NOT ACCEPTABLE AS SUBMITTED. PROVIDE
 ORIGINAL, LEGABLE DOCUMENTS, SIGNED AND
 SEALED BY STATE OF FLORIDA LICENSED ENG-
 INEER 104.2.3 CITY AMENDMENTS