| Plan Review Notes For Permit 99080492 |
| Permit Number |
99080492 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************* | | | | | | 1)NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT,MAINS,DISC.`S FUSES,BRKRS. | | | AS PER ARTS;110-9/215-5 | | | 2)NEED TO SUBMIT GROUNDING SYSTEM. | | | TO INCLUDE GROUNDING ELECTRODE SYSTEM | | | WITH ALL POINTS OF ATTACHMENT.ALSO | | | INCLUDE WIRE SIZES FIGURED FROM ART;/ | | | TABLE 250-94/250-95 | | | 3)NEED LOAD CALCULATIONS FOR EACH PANEL | | | AND FOR MDP.AS PER ART; 215-5 |
|