| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************PROVISO********************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING OF | | | EQUIPMENT AND BREAKERS. HAVE DRAWN ON | | | ROSER DDIAGRAM.AS PER ARTS;215-5,110-9 | | | 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | REQ`S SMOKE DETECTORS INSIDE AND | | | OUTSIDE ALL BEDROOMS IN NEW CONSTRUCTION | | | | | | NEEDS TO BE SUBMITTED AND APPROVED | | | BEFORE ROUGH ELECTRICAL INSPECTION. |
|