| Plan Review Notes For Permit 99080430 |
| Permit Number |
99080430 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE;NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT AND MAINS. AS PER ARTS;110-9/ | | | 215-5 | | | 2)NOTE;AS PER ART;250-81 GROUNDING | | | ELECTRODE CONDUCTOR IS REQ`D TO GO TO | | | BLDG.STEEL ALSO.\\ | | | 3)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS IN NEW | | | CONSTRUCTION OF DWELLINGS. | | | 4)NOTE: AS PER ART;210-8-A-6 ALL RECEPTS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 5)NOTE: AS PER ART 210-52 OUTLETS REQ`D | | | BEDROOM. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | TO BE APPROVED BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION. |
|