Plan Review Notes
Plan Review Notes For Permit 99080430
Permit Number 99080430
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE;NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS. AS PER ARTS;110-9/
 215-5
 2)NOTE;AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.\\
 3)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN NEW
 CONSTRUCTION OF DWELLINGS.
 4)NOTE: AS PER ART;210-8-A-6 ALL RECEPTS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE: AS PER ART 210-52 OUTLETS REQ`D
 BEDROOM.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 TO BE APPROVED BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION.