Plan Review Notes
Plan Review Notes For Permit 99080415
Permit Number 99080415
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*****************PROVISO***************
  
 1)NOTE;AS PER NFPA 1996/1993 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
 2)NOTE;NEED AIC RATING OF EQUIPMENT AND
 BREAKERS FIGURED FROM FAULT CURRENT
 CALCULATIONS.AS PER ARTS;110-9/215-5
 3)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE; ASPER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GOT TO BLDG.
 STEEL ALSO.
 5)NOTE:AS PER ART;210-52 2`6`12` RULE.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 TO BE APPROVED BEFORE FIRST ELECTRICAL
 ROUGH INSPECTION.