| Plan Review Notes For Permit 99080415 |
| Permit Number |
99080415 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************PROVISO*************** | | | | | | 1)NOTE;AS PER NFPA 1996/1993 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | 2)NOTE;NEED AIC RATING OF EQUIPMENT AND | | | BREAKERS FIGURED FROM FAULT CURRENT | | | CALCULATIONS.AS PER ARTS;110-9/215-5 | | | 3)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS. | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE; ASPER ART;250-81 GROUNDING | | | ELECTRODE CONDUCTOR TO GOT TO BLDG. | | | STEEL ALSO. | | | 5)NOTE:AS PER ART;210-52 2`6`12` RULE. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | TO BE APPROVED BEFORE FIRST ELECTRICAL | | | ROUGH INSPECTION. |
|