| Plan Review Notes For Permit 99080305 |
| Permit Number |
99080305 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: SAME AS FIRST SET OF NOTES. | | | NEED TO SHOW WHAT YOUR POWER SOURCE IS | | | ON THE THIRD FLOOR. YOU SAY INTERCEPTING | | | AS REQ`D ???? NEED TO SHOW WHERE THE | | | FEEDS ARE COMING FROM AND THE SIZE????" | | | | | | 2)NOTE: PLEASE SHOW ON LOAD CALCULATION | | | THE LOADS THAT ARE CONTINUOUS(LIGHING) | | | AND SHOW LOAD FIGURED AT 125%.ART 210-19 | | | 384-16C | | | | | | PLEASE SUBMIT THE ABOVE INFORMATON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS CALL | | | 659-8096 EXT 8372 |
|