| Plan Review Notes For Permit 99080305 |
| Permit Number |
99080305 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CLEARLY SHOW OCCUPANT LOAD ON PLANS TO | | | ENSURE COMPLIANCE W/SPC TABLE 407. | | | | | | CLEARLY SHOW WIDTH OF HANDICAP STALLS. | | | COMPLY W/FACBC SEC.4.17.3(EXCEPTION:NEW | | | CONSTRUCTION). | | | | | | WALLS AND FLOORS OF TOILET ROOMS SHALL | | | COMPLY W/SBC SEC.1204.2. | | | | | | OTHER TOILET ROOMS SHALL BE HANDICAP | | | ADAPTABLE PER FACBC SEC.4.1.3.(11). | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | A PERMANENT LADDER SHALL BE INSTALLED OR | | | HEATER SHALL BE INSTALLED ON FLOOR.(SEE | | | DEFINITION OF "READILY ACCESSIBLE"). | | | | | | INDICATE SLOPE OF PIPE ON PLANS PER SPC | | | SEC.705.2,705.3. | | | | | | SUBMIT ISOMETRIC FOR RWL SYSTEM . | | | SPC 104.2.1. | | | | | | SHT.P.02.-SHOW FIXTURE P-10 ON WATER | | | RISER.SPC 104.2.1. | | | | | | SUBMIT WATER RISER FOR AREAS SHOWN ON | | | SHT.P-02.SPC 104.2.1. | | | | | | SHOW TERMINATION PT.FOR 3" VENT FOR | | | TOILET ROOMS ON SHT P-1. |
|