| Plan Review Notes For Permit 99080267 |
| Permit Number |
99080267 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | | | | 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSDIE AND | | | OUTSIDE BEDROOMS IN NEW CONTRUCTION OF | | | HOMES. | | | 2)NOTE:AS PER ART;210-8-A-6 ALL RECEPTS. | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 3) NOTE:MASTER BEDROOM WALL INSIDE DOOR | | | REQ`S RECEPT.UNDER 210-52 | | | 4) NOTE:NEED TO SUBMIT AIC RATING OF | | | ALL EQUIPMENT, PANELS,DISC`S AND | | | BREAKERS, AS PER ARTS 110-9 AND 215-5 | | | 5) NOTE: GROUNDING ELECTRODE CONDUCTOR | | | REQ`D TO GO TO GRND. ROD AND BLDG.STEEL | | | AS PER ART 250-81 | | | | | | NEED TO HAVE PLANS SUBMITTED AND | | | APPROVED BEFORE ELECTRICAL ROUGH | | | INSPECTION. |
|