| Plan Review Notes For Permit 99080266 |
| Permit Number |
99080266 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | 1) NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | REQ`S FOR NEW CONSTRUCTION SMOKE | | | DETECTORS INSIDE AND OUTSIDE ALL | | | BEDROOMS. | | | 2) NOTE:AS PER 210-8-A-6 ALL RECEPTS. | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/ GFI PROTECTED. | | | 3) NOTE:GOUNDING ELECTRODE CONDUCTOR | | | TO GO TO BLDG.STEEL ALSO AS PER ART; | | | 250-81 | | | 4) NOTE:NEED TO SUBMIT AIC RATING OF | | | ALL EQUIPMENT AND RATING OF BREAKERS, | | | AS PER 110-9 AND 215-5 | | | | | | ALL THE ABOVE NEEDS TO BE SUBMITTED AND | | | APPROVED BEFORE ELECTRICAL ROUGH | | | INSPECTION. |
|