| Plan Review Notes For Permit 99080247 |
| Permit Number |
99080247 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT DETAILS FOR THE CAR CARE ISLANDS. | | | | | | SHT.B-1. HANDICAP STALLS SHALL COMPLY W/ | | | FACBC SEC.4.17.3.(SEE EXCEPTION:NEW | | | CONSTRUCTION.) | | | | | | CLEARLY SHOW REQUIRED MOUNTING HEIGHT | | | DIMENSIONS AND CLEAR FLOOR SPACE UNDER | | | PLBG.FIXTURES PER FACBC 1997 ED. | | | | | | SHOW FIXTURE CLEARANCES PER FACBC AND | | | SPC SEC.403.4.(SHOW CLEAR FLOOR ACCESS | | | FOR URINAL.SEE FACBC SEC.4.18.) | | | | | | A DRINKING FOUNTAIN IS REQD.PER SPC SEC. | | | 407.1.3. | | | | | | SINK SHALL COMPLY W/FACBC SEC.4.1.1(1)(A | | | 4.24.1 - 4.24.7. | | | | | | SUBMIT OCCUPANT LOAD.STRUCTURE SHALL | | | COMPLY W/SPC TABLE 407 FOR MINIMUM | | | TOILET FACILITIES.COMPLIANCE W/FLA. | | | STATUTE 553.141.MAY BE REQD.(POTTY | | | PARITY) | | | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC SEC.409.4.1.1. | | | | | | SUBMIT SANITARY AND WATER ISOMETRICS FOR | | | REVIEW PER SPC SEC.104.2.1. |
|