Plan Review Notes
Plan Review Notes For Permit 99080247
Permit Number 99080247
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00MAIN VENT IS REQUIRED FOR THE SANITARY
 SYSTEM PER SPC SEC.904.3.1.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC 914.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7(PERMANENT LADDER REQD.
 OR HEATER SHALL BE INSTALLED ON GROUND
 FLOOR.)SEE DEFIN.OF READILY ACCESSIBLE
 IN SEC.202.
  
 SUBMIT COPY OF WATER USE PERMIT FOR
 IRRIG.SYSTEM PER FLA.STATUTE 373.219 AND
 NOTE ON SHT LS-3.
  
 HANDICAP TOILET STALLS IN CLUBHOUSE
 SHALL COMPLY W/F.A.C.B.C. SEC.4.17.3
 (SEE EXCEPTION:NEW CONSTRUCTION.)
  
 SUBMIT ELEVATION DETAILS FOR PLUMBING
 FIXTURES.SHOW ALL REQD. MOUNTING HEIGHTS
 PER F.A.C.B.C.
  
 WALLS AND FLOORS OF TOILET ROOMS SHALL
 COMPLY W/SBC 1204.2
  
 FLOOR DRAINS ARE REQD.IN TOILET ROOMS
 PER SPC SEC.409.4.1.1
  
 SINK SHALL BE H.C.ACESSIBLE PER
 F.A.C.B.C.SEC.4.24.1-4.24.7, 4.1.1(1)(A)
  
 TOILET ROOM BY OFFICE SHALL BE H.C.
 ADAPTABLE PER F.A.C.B.C. 4.1.3.(11).
  
 A DRINKING FOUNTAIN IS REQD. PER
 TABLE 407.1.3.OF SPC.
  
 SUBMIT OCCUPANT LOAD PER SPC SEC.407.
 COMPLIANCE W/FLA.STATUTE 553.141 MAY BE
 REQD.(POTTY PARITY).