| Plan Review Notes For Permit 99080247 |
| Permit Number |
99080247 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | MAIN VENT IS REQUIRED FOR THE SANITARY | | | SYSTEM PER SPC SEC.904.3.1. | | | | | | CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/ | | | SPC 914.1. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7(PERMANENT LADDER REQD. | | | OR HEATER SHALL BE INSTALLED ON GROUND | | | FLOOR.)SEE DEFIN.OF READILY ACCESSIBLE | | | IN SEC.202. | | | | | | SUBMIT COPY OF WATER USE PERMIT FOR | | | IRRIG.SYSTEM PER FLA.STATUTE 373.219 AND | | | NOTE ON SHT LS-3. | | | | | | HANDICAP TOILET STALLS IN CLUBHOUSE | | | SHALL COMPLY W/F.A.C.B.C. SEC.4.17.3 | | | (SEE EXCEPTION:NEW CONSTRUCTION.) | | | | | | SUBMIT ELEVATION DETAILS FOR PLUMBING | | | FIXTURES.SHOW ALL REQD. MOUNTING HEIGHTS | | | PER F.A.C.B.C. | | | | | | WALLS AND FLOORS OF TOILET ROOMS SHALL | | | COMPLY W/SBC 1204.2 | | | | | | FLOOR DRAINS ARE REQD.IN TOILET ROOMS | | | PER SPC SEC.409.4.1.1 | | | | | | SINK SHALL BE H.C.ACESSIBLE PER | | | F.A.C.B.C.SEC.4.24.1-4.24.7, 4.1.1(1)(A) | | | | | | TOILET ROOM BY OFFICE SHALL BE H.C. | | | ADAPTABLE PER F.A.C.B.C. 4.1.3.(11). | | | | | | A DRINKING FOUNTAIN IS REQD. PER | | | TABLE 407.1.3.OF SPC. | | | | | | SUBMIT OCCUPANT LOAD PER SPC SEC.407. | | | COMPLIANCE W/FLA.STATUTE 553.141 MAY BE | | | REQD.(POTTY PARITY). |
|