Date Text
2001-01-08 00:00:00CORRECTED W/ 99100267 PERMIT APPL NCD
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1997 SMC 406.1 WITH NOTIFI-
 CATION BY BLDG FIRE ALARM OR HORN AND
 STROBE IF NO BLDG FIRE ALARM PER NFPA
 90A 4-4.4.3