Plan Review Notes
Plan Review Notes For Permit 99080187
Permit Number 99080187
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHOW LENGTH OF PIPING FROM POINT OF
 DELIVERY TO MOST REMOTE OUTLET ON GAS
 RISER.COMPLY W/STD.GAS CODE SEC.305.4
 (INDICATE SUPPLY PRESSURE)
  
 SANITARY RISER DOESN'T CORREELATE W/
 FLOOR PLAN.SPC 104.2.1.(POWDER ROOM)
  
 BAR SINK AND VEG.SINK MISSING ON SAN.
 RISER.
  
 MIN.SIZE SAN.LINE U/G SHALL BE 2" PER
 SPC SEC.714.4.