| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | 1)NOTE:1996 NFPA-72 REQ`S SMOKE | | | DETECTORS INSIDE AND OUTSIDE BEDROOMS. | | | 2)NOTE:NEED TO HAVE AIC RATING LISTED ON | | | PANEL SCHEDULE FOR EQUIPMENT AND BREAK- | | | ERS. ARTS,110-9 AND 215-5 | | | 3)NOTE:ART;373-8 STATES DISCS,PANELS,ETC | | | ARE NOT PERMITTED TO BE RACEWAYS. | | | | | | PLEASE CORRECT PLANS AND SUBMIT FOR | | | APPROVAL BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION. |
|