Plan Review Notes
Plan Review Notes For Permit 99080163
Permit Number 99080163
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00UNSAT SHT M-2
 (1) WTR HTR TOBE READLY ACCESSIBLE
 SEC 501.7 PROVIDE DETAIL OF SHIPS
 LADDER,OR PUT W/H ON GROUND FLOOR.
 (2) PAN DRAIN MIM. 1" SEC 507.8.2
 (3) TP RELIEF RUN SEPARATELY SEC 507.8.4
 (4) DWV ISOMETRIC, 2 W/C LEFT OUT.
 (5) TRAP PRIMERS ON FLR DRAINS IN
 PUBLIC REST RM'S SEC 409.4
 (6) TOILET STALLS:MEN'S & WOMEN'S
 REST RM'S TO COMPLY WITH FLORIDA
 ACCESSIBILITY CODE SEC 4.17.3 (1)
 SEE EXCEPTION.
 (7) SHT A-5 KITCHEN NOT A WORK AREA
 KITCHEN CABNETS TO BE 34" ABOVE FF
 FAC 4.24.1 & 4.24.7
 END OF COMMENTS