| Plan Review Notes For Permit 99080163 |
| Permit Number |
99080163 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | 1) PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2) DUCT SMOKE DETECTORS SHALL BE TIED | | | TO BUILDING FIRE ALARM FOR NOTIFICATION | | | PER NFPA 90A 4-4.4.2 OR IF NO BUILDING | | | FIRE ALARM SYSTEM, TIED TO HORN AND | | | STROBE PER NFPA 90A 4-4.4.3 |
|