| Plan Review Notes For Permit 99080096 |
| Permit Number |
99080096 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************DENIED***DENIED************* | | | | | | 1) NOTE;SHOW ALL ELECTRICAL LIGHTS, | | | RECEPTS,ETC. E-300 | | | 2)NOTE:NEED FIXTURE SCHEDULE OF FIX.TO | | | BE USED. | | | 3)NOTE:E-301 SHOW ALL ELECTRICAL WORK | | | LIGHTING,RECEPTS,EQUIPMENT BEING FED | | | ALL SIZES OF EQUIPMENT ETC. | | | 4)NOTE:E-600 RISER DIAGRAM TO BE | | | COMPLETE.!!!!!ARTS:215-5 110-9 | | | SHOW ALL WIRE SIZES,ALL CONDUIT SIZES, | | | GROUNDING ELECTRODE SYSTEM TO INCLUDE | | | GROUND RODS.BLDG.STEEL,CWP. | | | SHOW COMPLETE PANEL SCHEDULES WITH ALL | | | SIZES OF BRKS AND WIRE FEEDS. | | | AIC RATING OF ALL EQUIPMENT BEING USED | | | TO BE LISTED ON ALL PANEL SCHEDULES | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | AIC RATING OF FUSES,BRKS. | | | SHOW ALL TRANSFORMERS AND THEIR RATINGS. | | | GIVE COMPLETE LOAD CALCULATIONS OF ALL | | | DETAILED LOADS. | | | | | | ALL THE ABOVE MUST BE SUBMITTED FOR | | | APPROVAL. |
|