| Plan Review Notes For Permit 99080075 |
| Permit Number |
99080075 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | 1)NOTE:AS PER 110-9 AND 215-5,,NEED TO | | | SUBMIT AIC RATING OF ALL EQUIPMENT | | | AND BREAKERS ON RISER DIAGRAM. | | | 2) NOTE:AS PER ART 210-8-A-6 ALL RECEPTS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 3)NOTE:GROUNDING ELECTRODE CONDUCTOR | | | TO GO TO BLDG.STEEL ALSO AS PER 250-81 | | | 4)NOTE:MASTER BEDROOM OUTLETS AS REQ`D | | | PER 210-52 | | | 5)NOTE:AS PER 1996 NFPA-72 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | BEDROOMS. | | | | | | PLEASE HAVE THE ABOVE SUBMITTED AND | | | APPROVED BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION. |
|