| 2001-01-08 00:00:00 | CLEARLY SHOW ON PLANS THAT THE KITCHEN |
| | SINK COMPLIES W/FACBC SEC.4.24.1.- |
| | 4.24.7. |
| | |
| | A SERVICE SINK IS REQD.PER SPC TABLE 407 |
| | FOOTNOTE #15. |
| | |
| | SHOWERS SHALL BE PROVIDED PER SPC TABLE |
| | 407.(DORMITORIES)AND SHALL BE HANDICAP |
| | ACCESSIBLE PER FACBC SEC.4.21. |
| | |
| | CLEARLY SHOW ON PLANS THAT FLOORS AND |
| | WALLS IN COMMON AREA BATHROOMS AND |
| | TOILET ROOM COMPLY W/STD.BLDG.CODE SEC. |
| | 1204.2. |
| | |
| | FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT. |
| | PER PERSON (SLEEPING AREA ONLY) PER SPC |
| | TABLE 407.(SEE DORMITORIES). |
| | |
| | PLANS SHOW WATER CLOSETS INFRINGING ON |
| | WHEELCHAIR TURNING SPACE IN TOILET/BATH |
| | ROOMS.COMPLY W/FACBC SEC.4.2.3. |
| | |
| | SEPARATE FULLY ACCESSIBLE TOILET/BATH |
| | FACILITIES SHALL BE PROVIDED FOR MALES |
| | & FEMALES (COMMON AREA FACILITIES) PER |
| | FACBC SEC.4.1.3.(11), 4.22, 9.2(E). |
| | |
| | AN APPROVED BFP DEVICE IS REQD.ON THE |
| | MAKE-UP WATER LINE TO THE COOLING TOWER. |
| | SPC SEC.606.1. |
| | |
| | A GREASE INTERCEPTOR IS REQD.PER SPC |
| | SEC.1004.1, 1004.2, 1004.4.CONTACT ROD |
| | COMPO AT CITY OF W.P.B. REGIONAL WASTE- |
| | WATER TREATMENT PLANT FOR SIZE REQS. |
| | (561) 835-7423. |
| | |
| | SHT.P-8-WATER HEATER PAN DAIN AND RELIEF |
| | LINE SHALL NOT BE COMBINED PER COUNTY- |
| | WIDE AMENDMENTS TO STD.PLBG.CODE SECS.. |
| | 507.8.3, 507.8.4. |
| | |
| | OCCUPANCY SHALL BE DETERMINED BY THE |
| | BUILDING OFFICIAL PER SBC SEC.301.3. |
| | AND THE BUILDING OFFICIAL SHALL RENDER |
| | INTERPRETATIONS PER SBC SEC.103.1(RE: |
| | IS OCCUPANCY A DWELLING OR DORMITORY?) |
| | |
| | ALL ADDENDUMS TO PLANS SHALL BE ATTACHED |
| | TO THE PLANS |