| Date |
Text |
| 2001-01-08 00:00:00 | NOTES CORRECTED ON REVISION | | | 1)PROVIDE BACKDRAFT DAMPERS AT EACH | | | EXHAUST FAN RUNOUT TO PREVENT CARRYOVER | | | INTO ROOMS WITHOUT CEILING MOUNTED EXHAU | | | ST FANS FROM ROOMS WITH CEILING MOUNTED | | | EXHAUST FANS WHEN ROOF MOUNTED EXHAUST | | | FANS ARE NOT RUNNING 1997 SMC 501.4 | | | 2) IF HP-F IS USING ABOVE CEILING FOR | | | RETURN AIR PLENUM, AIR ADMITTANCE VALVES | | | 'SHALL NOT BE USED IN SAME SPACE. SMC | | | 609.1.3 | | | 3)ANY A/C UNITS SERVING AREA USED FOR | | | EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE | | | DETECTOR 1997 SMC 406.2 | | | 4)EVERY ATTIC IN WHICH MECHANICAL EQUIP- | | | MENT IS INSTALLED SHALL BE ACCESSIBLE BY | | | AN OPENING AS LARGE AS THE LARGEST PIECE | | | OF EQUIPMENT BUT IN NO CASE LESS THAN | | | 22X36 INCHES. 1997 SMC 304.4.1 |
|