| Date |
Text |
| 2001-01-08 00:00:00 | CLEARLY SHOW ON PLANS THAT KITCHEN SINK |
| | COMPLIES W/FACBC SEC.4.24.1- 4.24.7. |
| | |
| | A SERVICE SINK IS REQD.PER SPC TABLE 407 |
| | FOOTNOTE #15. |
| | |
| | SHOWERS SHALL BE PROVIDED PER SPC TABLE |
| | 407 (DORMITORIES) AND SHALL BE HANDICAP |
| | ACCESSIBLE PER FACBC SEC.4.21. |
| | |
| | CLEARLY SHOW WALLS AND FLOORS IN COMMON |
| | AREA BATHROOMS AND TOILET ROOM COMPLY W/ |
| | STD.BLDG.CODE SEC.1204.2. |
| | |
| | FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT. |
| | PER PERSON (SLEEPING AREA ONLY)PER |
| | TABLE 407 OF SPC. |
| | |
| | PLANS SHOW WATER CLOSETS INFRINGING ON |
| | WHEELCHAIR TURNING SPACE IN TOILET/BATH |
| | ROOMS.COMPLY W/FACBC SEC.4.2.3. |
| | |
| | SEPARATE FULLY ACCESSIBLE TOILET/BATH |
| | FACILITIES SHALL BE PROVIDED FOR MALES |
| | & FEMALES(COMMON AREA FACILITIES) PER |
| | FACBC SEC.4.1.3(11), 4.22, 9.2(E). |
| | |
| | AN APPROVED BFP DEVICE IS REQD.ON THE |
| | MAKE-UP WATER LINE TO THE COOLING TOWER. |
| | SPC SEC.606.1. |
| | |
| | A GREASE INTERCEPTOR IS REQD.PER SPC |
| | SEC.1004.1,1004.2,1004.4.CONTACT RODNEY |
| | COMPO AT CITY OF W.P.B. REGIONAL WASTE- |
| | WATER TREATMENT PLANT FOR SIZE REQS. |
| | (561)835-7423. |
| | |
| | SHT.P-8-WATER HEATER DRAIN PAN AND |
| | RELIEF LINE SHALL NOT BE COMBINED PER |
| | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE |
| | SECS.507.8.3, 507.8.4. |
| | |
| | OCCUPANCY SHALL BE DETERMINED BY THE |
| | BUILDING OFFICIAL PER SBC SEC.301.3 AND |
| | THE BUILDING OFFICIAL SHALL RENDER |
| | INTERPRETATIONS PER SBC SEC.103.1(RE: |
| | IS OCCUPANCY TO BE CLASSED AS A DWELLING |
| | OR A DORMITORY?) |
| | |
| | ALL SUBMITTED ADDENDUMS SHALL BE |
| | ATTACHED TO THE PLANS. |