| Plan Review Notes For Permit 99080038 |
| Permit Number |
99080038 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | 1) PROVIDE BACKDRAFT DAMPERS AT EACH | | | EXHAUST FAN RUNOUT TO PREVENT CARRYOVER | | | INTO ROOMS WITHOUT CEILING MOUNTED EXHAU | | | ST FANS FROM ROOMS WITH CEILING MOUNTED | | | EXHAUST FANS WHEN ROOF MOUNTED EXHAUST | | | FANS ARE NOT RUNNING 1997 SMC 501.4 | | | 2) IF HP-F IS USING ABOVE CEILING FOR | | | RETURN AIR PLENUM, AIR ADMITTANCE VALVES | | | SHALL NOT BE USED IN SAME SPACE | | | 3) ANY A/C UNITS SERVING AREA USED FOR | | | EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE | | | DETECTOR 1997 SMC 406.2 | | | 4) EVERY ATTIC IN WHICH MECHANICAL EQUIP | | | MENT IS INSTALLED SHALL BE ACCESSIBLE BY | | | AN OPENING AS LARGE AS THE LARGEST PIECE | | | OF EQUIPMENT BUT IN NO CASE LESS THAN | | | 22X36 INCHES. |
|