| Plan Review Notes For Permit 99080036 |
| Permit Number |
99080036 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHOWERS SHALL BE PROVIDED PER SPC TABLE | | | 407.(SEE REQS.FOR DORMITORIES.) | | | | | | CLEARLY SHOW ON PLANS THAT FLOORS AND | | | WALLS IN COMMON AREA BATHROOMS AND | | | TOILET ROOMS COMPLY W/SBC SEC.1204.2. | | | | | | SIZE REQUIREMENT AND DESIGN OF GREASE | | | TRAP SHALL COMPLY W/HEALTH DEPT.REQS. | | | AND CITY OF WEST PALM BEACH UTILITIES. | | | CONTACT RODNEY COMPO AT CITY OF WPB | | | REGIONAL WASTEWATER TREATMENT FACILITY. | | | SEEFLA.ADMIN.CODE SEC.64E-6.013(5)(A). | | | | | | CLEARLY SHOW ON PLAN THAT GREASE TRAP | | | WILL NOT BE LOCATED WITHIN ANGLE OF | | | REPOSE. | | | | | | MINIMUM INLET AND OUTLET TO GREASE TRAP | | | SHALL BE 4" AND INLET SHALL DISCHARGE A | | | MIN.OF 2 1/2" ABOVE LIQUID LEVEL LINE. |
|