| Date |
Text |
| 2001-01-08 00:00:00 | THE OCCUPANCY OF THE STRUCTURE SHALL BE |
| | DETERMINED BY THE BUILDING OFFICIAL PER |
| | SBC SEC.301.3 AND THE BUILDING OFFICIAL |
| | SHALL RENDER INTERPRETATIONS PER SBC |
| | SEC.103.1.(RE:IS OCCUPANCY TO BE CLASSED |
| | AS A DWELLING OR A DORMITORY.?) |
| | |
| | CLEARLY SHOW ON THE PLANS THAT THE |
| | KITCHEN SINK COMPLIES W/FACBC SEC.4.24.1 |
| | THRU 4.24.7. |
| | |
| | SHOWERS SHALL BE PROVIDED PER SPC TABLE |
| | 407(DORMITORIES) AND SHALL BE HANDICAP |
| | ACCESSIBLE PER SBC 4.21. |
| | |
| | CLEARLY SHOW ON THE PLANS THAT FLOORS |
| | AND WALLS IN COMMON AREA BATHROOMS AND |
| | TOILET ROOMS COMPLY W/SBC SEC.1204.2 |
| | |
| | FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT. |
| | PER PERSON (SLEEPING AREA ONLY) PER |
| | TABLE 407 OF SPC. |
| | |
| | SHT.M-5-AN APPROVED BACKFLOW PREVENTION |
| | DEVICE SHALL BE INSTALLED IN THE MAKE-UP |
| | WATER LINE TO THE COOLING TOWER PER SBC |
| | SEC.606.1-606.5 |
| | |
| | A GREASE INTERCEPTOR IS REQD.PER SPC SEC |
| | 1004.1, 1004.2.,1004.4.CONTACT RODNEY |
| | COMPO AT CITY OF W.P.B. REGIONAL WASTE- |
| | WATER TREATMENT FACILITY FOR SIZE |
| | REQS. |
| | |
| | SHT.P-8-WATER HEATER PAN DRAIN AND |
| | RELIEF LINE SHALL NOT BE COMBINED PER |
| | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE |
| | SEC.507.8.3,507.8.4. |
| | |
| | SUBMIT COPY OF COMPLETED APPLICATION OF |
| | WATER USE PERMIT FROM SO.FLA.WTR.MNGMT. |
| | (MUST HAVE AGENCY'S STAMP OF RECEIPT ON |
| | APPLICATION.)SPC 101.4.7,FLA.STATUTE |
| | 373.62. |
| | |
| | CORRECTIONS TO PLANS TO BE MADE ON LARGE |
| | SHEETS AND ADDENDUMS SHALL BE ATTACHED |
| | TO THE PLANS. |