| 2001-01-08 00:00:00 | 1) THE NEW ENTRY DRIVE IS TO BE AT LEAST | | | 20 FEET IN CLEAR WIDTH. | | | 2) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON PLANS. CUT SHEETS, WIRING | | | DIAGRAM AND FLOOR PLANS ARE TO BE | | | SUBMITTED. | | | | | | ON NOVEMBER 27,2000, WRITER SPOKE TO | | | KEVIN NORTH OF THE WEITZ COMPANY. | | | PER MR. NORTH, THE BUILDING WILL BE | | | COMPLETELY FIRE SPRINKLER PROTECTED AND | | | THE FP PLANS WERE PREVIOUSLY SUBMITTED | | | TO THE CITY. MR. NORTH WAS ADVISED THAT | | | THE FIRE SPRINKLER SYSTEM CONNECTION IS | | | TO BE WITHIN 150 FEET OF THE FIRE | | | HYDRANT. PLANS WERE PREVIOUSLY APPROVED | | | BY FIRE RESCUE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|