| Plan Review Notes For Permit 99080036 |
| Permit Number |
99080036 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. STORMWATER CALCULATIONS ARE STILL | | | REQUIRED, SUPPLY PRIOR TO START OF | | | CONSTRUCTION. USE THE FOLLOWING AS A | | | GUIDE LINE: | | | BUILDING AREA | | | +PAVED AREA | | | TOTAL IMPERVIOUS AREA | | | +TOTAL GREEN AREA | | | TOTAL SITE AREA | | | TOTAL IMPERVIOUS AREA (IN SF): | | | DIVIDED BY 1,573 SF (1 ERU EQUALS THE | | | ERU'S TO BE CHARGED | | | TOTAL IMPERVIOUS AREA NEEDS TO BE IN | | | ERU'S. | | | 43,560 SQUARE FEET IN AN ACRE | | | 1,573SQUARE FEET 1 ERU | | | 27.692308 ERU'S PER ACRE. | | | ERU (EQUIVALENT RESIDENTIAL UNIT)IS AN | | | INPURMEATABLE SURFACES, SUCH AS ROOFS, | | | SIDEWALKS, PARKING LOTS. | | | | | | | | | 2. PLANS ARE STILL WRONG ON WATER | | | SERVICE.IT MUST BE A TAPPING VALVE AND | | | SLEEVE, 4" WATER SERVICE WITH BYPASS, 3" | | | METER THEN THE REDUCED PRESSURE | | | PRINCIPLE BACKFLOW PREVENTERS.THE | | | DRAWING DOES NOT STATE IT BUT IT IS | | | SUGGESTED THAT TWO DEVICES BE INSTALLED | | | IN PARALLEL SO THE BUILDINGS ARE NEVER | | | WITHOUT SERVICE. | | | | | | 3. SHEET SP-1 DOES NOT SHOW THE OPENING | | | BETWEEN THE DUMPSTER GATES.THE OPENING | | | BETWEEN THE GATES MUST BE 12' - 6". |
|