Plan Review Notes
Plan Review Notes For Permit 99071835
Permit Number 99071835
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00INDICATE TYPE OF GAS AND PIPING TO BE
 INSTALLED PER STD.GAS CODE SEC.302..
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 (SEE DEFINITION IN CHAPT.2.)AND SHALL BE
 EQUIPPED W/A PAN DRAIN PER SPC SEC.
 507.8.1.
  
 FLOOR DRAINS SHALL NOT EXCEED DISTANCE
 FROM VENT PER SPC TABLE 908.
  
 DRAIN FROM ICE MACHINE SHALL BE
 INDIRECTLY WASTED PER SPC SEC.804.1.
 (SIZE ALL INDIRECT WASTES ON PLANS.)
  
 HAND SINKS SHALL DISCHARGE TO GREASY
 WASTE SYSTEM PER SPC SEC.1004.4.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIP.PER
 STD.GAS CODE SEC.402.1.
  
 MAIN VENT REQ'D.FOR SANITARY SYSTEM PER
 SPC SEC.904.3.1.