| | CHECKLIST FOR PROVISO SUBMITTAL: |
| | |
| | 1-ENTRY EGRESS DOOR TO HAVE 32" MINIMUM |
| | CLEAR OPENING. TABLE 1004 SBC 1997. |
| | 2-PROVIDE PRODUCT APPROVAL AND COMPLETE |
| | INSTALLATION DETAILS AND SPECIFICATIONS |
| | FOR FRAME AND BUTT GLAZING WINDOW. |
| | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97. |
| | 3-PROVIDE THE DESIGN PRESSURES AT ALL |
| | EXTERIOR OPENINGS. SEC. 1606 SBC 1997. |
| | 4-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. MEAN |
| | ROOF HEIGHT IS NOT CORRECT. |
| | 5-STRUCTURAL ENGINEER OF RECORD TO SIGN |
| | SEAL AND DATE THE REVISED STRUCTURAL |
| | DRAWINGS. SEC 104.2 CITY AMENDMENTS. |
| | 6-PROVIDE COMPLETE INSTALLATION/DETAIL |
| | FOR AHU'S. COMPLETELY SPECIFY ALL |
| | HANGERS AND CONNECTORS. SEC 104.2.2 |
| | CITY AMENDMENTS. |
| | 7-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOORS WITH SIDELITES ASSEMBLY, ROUND |
| | AND OVAL WINDOWS, BUTT GLAZING. |
| | 8-20"X20"X24"HIGH CONCRETE BLOCK |
| | PLATFORM IS ACCEPTABLE FOR PROTECTION |
| | OF GWH IN GARAGE BUT NEED TO SPECIFY |
| | THAT CONCRETE BLOCK CELLS NEED TO BE |
| | FILLED (SPECIFY HOW TO BE FILLED). |
| | 9- SEE PLANS FOR ADDITIONAL COMMENTS BY |
| | BUILDING PLAN REVIEWER AND THE OTHER |
| | TRADES COMMENTS. |
| | 10-ENGINEERED TRUSS DRAWINGS NEED TO |
| | BE DESIGNED USING SBC 1997 OR ASCE 7-95 |
| | -UPDATE ALL DETAILS AND LETTERS PACKAGE |
| | SUBMITTED. CITY HAS ADOPTED 1997 SBC. |
| | -ENGINEER TO DATE THE DAY HE SIGNS AND |
| | SEALS THE DOCUMENTS. |
| | |
| | NOTE: PLEASE RETURN THE REVIEWED SET OF |
| | DRAWINGS IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS. |