| Plan Review Notes For Permit 99071788 |
| Permit Number |
99071788 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********2ND REVIEWPROVISO DENIED** | | | | | | 1)NOTE: STILL NEED TO SUBMIT AIC RATING | | | OF EQUIPMENT BEING INSTALLED.!! | | | AIC RATINGS CAN BE FIGURED FROM DOING | | | FAULT CURRENT CALCULATIONS,AS PER ARTS: | | | 110-9/215-5 | | | 2)NOTE:ON ELECTRICAL RISER DIAGRAM YOU | | | SHOW EQUIPMENT GROUND BEING INSTALLED | | | FROM METER TO DISC..EQUIPMENT GROUNDING | | | CONDUCTOR IS ONLY TO BE INSTALLED AFTER | | | FIRST MEANS OF DISC. | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. |
|