| Plan Review Notes For Permit 99071771 |
| Permit Number |
99071771 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | | | | 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | REQ.SMOKE DETECTORS INSIDE AND OUTSIDE | | | ALL BEDROOMS IN NEW CONSTRUCTION HOMES. | | | 2)NOTE:AS PER ART 210--8-A-6 REQ. ALL | | | RECEPTS. SERVING KITCHEN COUNTER SPACE | | | TO BE GFI. | | | 3)NOTE AS PER ART:250-81 GROUNDING | | | ELECTRODE CONDUCTOR REQ. TO BLDG.STEEL. | | | 4)NOTE:AS PER ART,210-52 LIVING ROOM | | | REAR WALLS REQ.OUTLETS 2`,6`,12` RULE, | | | PLEASE CORRECT. | | | 5) NOTE:AS PER ART 210-52E REQ`S OUTLETS | | | AT THE FRONT AND REAR OF NEW HOUSES | | | 6)NOTE:AHU#1 IS SHOWN AT MASTER BEDROOM | | | SIDE OF HOUSE,,NO COND.UNIT SHOWN,, | | | PLEASE DRAW IN WITH DISC,AS REQ`D PER | | | 440-11 AND SHOW WP GFI AS PER 210-63 | | | 7)NOTE:ELECTRICAL FOR SPA/WHIRLPOOL TUB | | | IS TO BE GFI/GFI PROTECTED. | | | 8)NOTE:NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT!!PANELS,DISC`S AND BREAKERS. | | | AS PER ARTS;110-9 AND 215-5 | | | 9)NOTE:AS PER ART;210-52G GARAGE GFI. | | | REQ`D. | | | | | | ALL THE ABOVE NEEDS TO BE SUBMITTED | | | AND APPROVED BEFORE FIRST ELECTRICAL | | | ROUGH INSPECTION!! |
|