2001-01-08 00:00:00*************PROVISO********************
  
 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 REQ.SMOKE DETECTORS INSIDE AND OUTSIDE
 ALL BEDROOMS IN NEW CONSTRUCTION HOMES.
 2)NOTE:AS PER ART 210--8-A-6 REQ. ALL
 RECEPTS. SERVING KITCHEN COUNTER SPACE
 TO BE GFI.
 3)NOTE AS PER ART:250-81 GROUNDING
 ELECTRODE CONDUCTOR REQ. TO BLDG.STEEL.
 4)NOTE:AS PER ART,210-52 LIVING ROOM
 REAR WALLS REQ.OUTLETS 2`,6`,12` RULE,
 PLEASE CORRECT.
 5) NOTE:AS PER ART 210-52E REQ`S OUTLETS
 AT THE FRONT AND REAR OF NEW HOUSES
 6)NOTE:AHU#1 IS SHOWN AT MASTER BEDROOM
 SIDE OF HOUSE,,NO COND.UNIT SHOWN,,
 PLEASE DRAW IN WITH DISC,AS REQ`D PER
 440-11 AND SHOW WP GFI AS PER 210-63
 7)NOTE:ELECTRICAL FOR SPA/WHIRLPOOL TUB
 IS TO BE GFI/GFI PROTECTED.
 8)NOTE:NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT!!PANELS,DISC`S AND BREAKERS.
 AS PER ARTS;110-9 AND 215-5
 9)NOTE:AS PER ART;210-52G GARAGE GFI.
 REQ`D.
  
 ALL THE ABOVE NEEDS TO BE SUBMITTED
 AND APPROVED BEFORE FIRST ELECTRICAL
 ROUGH INSPECTION!!