Plan Review Notes
Plan Review Notes For Permit 99071415
Permit Number 99071415
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.A-4.-SIZE THE WATER RISER TO THE
 TOILET ROOMS.COMPLY W/SPC SEC.607.1
  
 FLOOR SINK IS NOT INDICATED ON THE WATER
 RISER ON SHT.A-4.
  
 CLEARLY SHOW TOTAL LINEAL FEET TO MOST
 REMOTE OUTLET ON GAS SYSTEM PER STD.GAS
 CODE SEC.305.4
  
 INDICATE TYPE OF MATERIAL TO BE UTILIZED
 FOR THE GAS PIPING SYSTEM.STD.GAS CODE
 SEC.306.
  
 INDICATE GAS SUPPLY PRESSURE ON PLANS
 AND DISTANCE OF METER FROM BUILDING PER
 STD.GAS CODE SEC. 305.2
  
 SHT.A-5-GAS LINE SHALL BE SIZED PER STD.
 GAS CODE SEC.305.4A.(TABLE DOESN'T SHOW
 3 1/2"PIPE)
  
 DRINKING FOUNTAIN SHALL COMPLY W/
 F.A.C.B.C. SEC.4.1.3(10)(A).
  
 PRIVATE TOILET ROOM SHALL BE H.C.
 ADAPTABLE PER F.A.C.B.C. SEC.4.1.3(11).
  
 SUBMIT MANUF.SHEETS FOR EPOXY PAINT TO
 ENSURE COMPLIANCE W/SBC SEC.1204.2(NON-
 ABSORBENT.)
  
 CALCULATIONS FOR COMBUSTION AIR SHALL BE
 DETERMINED FROM STD.GAS CODE SEC. 402.