| Plan Review Notes For Permit 99071415 |
| Permit Number |
99071415 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHT.A-4.-SIZE THE WATER RISER TO THE | | | TOILET ROOMS.COMPLY W/SPC SEC.607.1 | | | | | | FLOOR SINK IS NOT INDICATED ON THE WATER | | | RISER ON SHT.A-4. | | | | | | CLEARLY SHOW TOTAL LINEAL FEET TO MOST | | | REMOTE OUTLET ON GAS SYSTEM PER STD.GAS | | | CODE SEC.305.4 | | | | | | INDICATE TYPE OF MATERIAL TO BE UTILIZED | | | FOR THE GAS PIPING SYSTEM.STD.GAS CODE | | | SEC.306. | | | | | | INDICATE GAS SUPPLY PRESSURE ON PLANS | | | AND DISTANCE OF METER FROM BUILDING PER | | | STD.GAS CODE SEC. 305.2 | | | | | | SHT.A-5-GAS LINE SHALL BE SIZED PER STD. | | | GAS CODE SEC.305.4A.(TABLE DOESN'T SHOW | | | 3 1/2"PIPE) | | | | | | DRINKING FOUNTAIN SHALL COMPLY W/ | | | F.A.C.B.C. SEC.4.1.3(10)(A). | | | | | | PRIVATE TOILET ROOM SHALL BE H.C. | | | ADAPTABLE PER F.A.C.B.C. SEC.4.1.3(11). | | | | | | SUBMIT MANUF.SHEETS FOR EPOXY PAINT TO | | | ENSURE COMPLIANCE W/SBC SEC.1204.2(NON- | | | ABSORBENT.) | | | | | | CALCULATIONS FOR COMBUSTION AIR SHALL BE | | | DETERMINED FROM STD.GAS CODE SEC. 402. |
|