| Plan Review Notes For Permit 99071361 |
| Permit Number |
99071361 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO****************** | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON WET VENTS PER COUNTYWIDE | | | AMENDMENT TO SPC SEC.911.1.1. | | | | | | SANITARY RISER DOESN'T CORRELATE W/FLOOR | | | PLAN.SUBMIT REVISED SANITARY RISER PRIOR | | | TO ROUGH PLBG.INSPECTION.COUNTYWIDE | | | AMENDMENT TO SPC SEC.104.2.1. |
|