2001-01-08 00:00:00************ UNSAT ********************
  
 1)NOTE:AS REQ`D BY ART;250-81 OF THE NEC
 ALL OF THE FOOLOWING ARE TO BE INCLUDED
 FOR THE GROUNDING ELECTRODE SYSTEM.
 1.GROUND ROD,COLD WATER PIPE AND BLDG.
 STEEL. ALL THREE NEED TO BE SHOWN ON
 THE RISER DIAGRAM.
  
 2)NOTE: IF CONDUIT BETWEEN MAIN DISC AND
 PANEL IS PVC THEN THERE NEEDS TO BE
 AN EQUIPMENT GROUNDING CONDUCTOR INSTALL
 -ED. SIZE PER 250-95