| Plan Review Notes For Permit 99071295 |
| Permit Number |
99071295 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BREAKROOM SINKS SHALL COMPLY W/F.A.C.B.C | | | SEC.4.24.1 - 4.24.7. | | | | | | ROOMS #106 & 107-THE ACESSIBLE WATER | | | CLOSET SHALL BE DIAGONAL TO THE DOOR PER | | | F.A.C.B.C.SEC 4.17.3(2). | | | | | | ACCESIBLE D.F.SHALL COMPLY W/F.A.C.B.C. | | | SEC.4.1.3.(10)(A). | | | | | | STAFF TOILETS SHALL BE HANDICAP ACCESS- | | | IBLE PER F.A.C.B.C.SEC.4.1.2(6). | | | | | | FLOOR DRAIN IS REQ'D.IN THE STAFF TOILET | | | ROOM PER SPC SEC.409.4.1.1 | | | | | | WALLS IN RESTROOMS AND STAFF TOILET | | | SHALL BE NON-ABSORBENT MATERIAL PER SBC | | | SEC.1204.2. | | | | | | SHT.A-6-SHOW MOUNTING HEIGHTS OF | | | ALL HANDICAP FIXTURES AND ACCESSORIES. | | | COMPLY W/F.A.C.B.C. | | | | | | SHOWER IN STAFF BATHROOM SHALL COMPLY W/ | | | F.AC.B.C. SEC.4.21.1. | | | | | | SUBMIT STORM DRAINAGE RISER FOR REVIEW. | | | COMPLY W/SPC SEC.1108. | | | | | | ROOF SYSTEM SHALL BE SUPPLIED W/ | | | PROVISIONS FOR SECONDARY DRAINAGE PER | | | SPC SEC.1109. | | | | | | CIRCUIT AND LOOP VENTING SYSTEM SHALL | | | COMPLY W/SPC SEC.914.1. | | | | | | INDICATE SLOPE OF SANITARY PIPING ON | | | PLAN.COMPLY W/SPC 714.1,714.2. |
|