Plan Review Notes
Plan Review Notes For Permit 99071295
Permit Number 99071295
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00BREAKROOM SINKS SHALL COMPLY W/F.A.C.B.C
 SEC.4.24.1 - 4.24.7.
  
 ROOMS #106 & 107-THE ACESSIBLE WATER
 CLOSET SHALL BE DIAGONAL TO THE DOOR PER
 F.A.C.B.C.SEC 4.17.3(2).
  
 ACCESIBLE D.F.SHALL COMPLY W/F.A.C.B.C.
 SEC.4.1.3.(10)(A).
  
 STAFF TOILETS SHALL BE HANDICAP ACCESS-
 IBLE PER F.A.C.B.C.SEC.4.1.2(6).
  
 FLOOR DRAIN IS REQ'D.IN THE STAFF TOILET
 ROOM PER SPC SEC.409.4.1.1
  
 WALLS IN RESTROOMS AND STAFF TOILET
 SHALL BE NON-ABSORBENT MATERIAL PER SBC
 SEC.1204.2.
  
 SHT.A-6-SHOW MOUNTING HEIGHTS OF
 ALL HANDICAP FIXTURES AND ACCESSORIES.
 COMPLY W/F.A.C.B.C.
  
 SHOWER IN STAFF BATHROOM SHALL COMPLY W/
 F.AC.B.C. SEC.4.21.1.
  
 SUBMIT STORM DRAINAGE RISER FOR REVIEW.
 COMPLY W/SPC SEC.1108.
  
 ROOF SYSTEM SHALL BE SUPPLIED W/
 PROVISIONS FOR SECONDARY DRAINAGE PER
 SPC SEC.1109.
  
 CIRCUIT AND LOOP VENTING SYSTEM SHALL
 COMPLY W/SPC SEC.914.1.
  
 INDICATE SLOPE OF SANITARY PIPING ON
 PLAN.COMPLY W/SPC 714.1,714.2.