Plan Review Notes
Plan Review Notes For Permit 99071295
Permit Number 99071295
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*****************
  
 1)NOTE:SHEET E-3 OUTLET SPACING TO MEET
 LOCAL PALM BEACH COUNTY AMENDMENTS ART:
 210-50D 12`OF UNENCUMBERED WALL SPACE
 IN OFFICE AND EVERY 20` FOR STORAGE
 AREAS .
 2) NOTE:SHEET E-2 RISER DIAGRAM SHOWS
 PANEL NSCA FEEDING NSCB WITH 50 AMP
 OVERCURRENT PROTECTION, BUT SHEET E-7
 NSCA PANEL SCEDULE SHOWS 125A FEED.
 PLEASE CORRECT.
 3)NOTE:SHEET E-2 ALSO SHOWS NSCA FEEDING
 NSCC WITH 70AMP OVERCURRENT PROTECTION
 YET SHEET E-7 SHOWS 125A BRK.
  
 PLEASE HAVE CORRECTIONS MADE AND
 SUBMITTED FOR APPROVAL BEFORE ROUGH
 INSPECTION.