| Plan Review Notes For Permit 99071267 |
| Permit Number |
99071267 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | COOLER DENIEDPROVIDE INFORMATION ON | | | WIND LOAD AND WEATHER PROTECTION | | | HOOD APPROVED PROVISO: HOOD USE ONLY | | | FOR CABINET TYPE OVENS WHICH DO NOT HEAT | | | THE FOOD PRODUCT CORE TO A TEMPERATURE | | | ABOVE 212 DEGREE F | | | PROVIDE PATH FOR SUPPLY AIR TO COMPLY | | | WITH 1994 SMC 501.2 PRESSURE EQUILIZA- | | | TIONTO MAKE UP FOR AIR EXHAUSTED BY | | | HOOD |
|