Plan Review Notes
Plan Review Notes For Permit 99071192
Permit Number 99071192
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00ALL FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 LAYOUT OF FIXTURES IN 1ST.FLR.POWDER
 BATH ON RISER DOESN'T MATCH ARCH.FLOOR
 PLAN.SPC 104.2.1.
  
 INDICATE TYPE OF PIPE USED FOR GAS
 SYSTEM,DISTANCE TO MOST REMOTE OUTLET,
 BTU LOAD OF EACH APPLIANCE & TOTAL BTU
 LOAD ON THE SYSTEM PER STD. GAS CODE
 SEC.302, 305.2,305.4.