Plan Review Notes
Plan Review Notes For Permit 99071179
Permit Number 99071179
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: NEEDS TO HAVE ZONING APPROVAL
 FOR SECOND METER.
  
 2)NOTE: NEED TOHAVE THE BATH CIRCUIT
 LISTED ON PANEL SCHEDULE AS PER THE REQ`
 MENTS OF 210-11-C-3 NEEDS TO BE 20AMP
 AND #12.
  
 3)NOTE: NEED TO HAVE SMOKE DETECTORS
 INSTALLED PER NFPA-72 2-2.1.1.1
 INSIDE AND OUTSIDE BEDROOMS.
  
 4)NOTE;AS PER 250-50 NEED TO HAVE THE
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 THE BLDG. STEEL OF NEW STRUCTURE.PLEASE
 SHOW THIS ON THE RISER DIAGRAM. PER 215-
 -5.YOU ALSO MUST GO TO ANY METALCOLD
 WATER PIPE FOR BOND.
  
 5)NOTE: YOU SHOW THE AIC RAITN FOR THE
 PANEL BUT NOT FOR THE MAIN DISCONNECT
 SHOWN?? PLEASE SUBMIT THE AIC RATING FOR
 MAIN DISC, PER 110-9/215-5.
  
 6)NOTE: PLEASE SHOW THE OUTSIDE RECEPT
 AS GFI AS REQ`D BY 210-8
  
 7)NOTE : NEED TO SUBMIT TWO SETS OF
 PLANS.
  
  
 NEED TO SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372