| Plan Review Notes For Permit 99071179 |
| Permit Number |
99071179 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: NEEDS TO HAVE ZONING APPROVAL | | | FOR SECOND METER. | | | | | | 2)NOTE: NEED TOHAVE THE BATH CIRCUIT | | | LISTED ON PANEL SCHEDULE AS PER THE REQ` | | | MENTS OF 210-11-C-3 NEEDS TO BE 20AMP | | | AND #12. | | | | | | 3)NOTE: NEED TO HAVE SMOKE DETECTORS | | | INSTALLED PER NFPA-72 2-2.1.1.1 | | | INSIDE AND OUTSIDE BEDROOMS. | | | | | | 4)NOTE;AS PER 250-50 NEED TO HAVE THE | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | THE BLDG. STEEL OF NEW STRUCTURE.PLEASE | | | SHOW THIS ON THE RISER DIAGRAM. PER 215- | | | -5.YOU ALSO MUST GO TO ANY METALCOLD | | | WATER PIPE FOR BOND. | | | | | | 5)NOTE: YOU SHOW THE AIC RAITN FOR THE | | | PANEL BUT NOT FOR THE MAIN DISCONNECT | | | SHOWN?? PLEASE SUBMIT THE AIC RATING FOR | | | MAIN DISC, PER 110-9/215-5. | | | | | | 6)NOTE: PLEASE SHOW THE OUTSIDE RECEPT | | | AS GFI AS REQ`D BY 210-8 | | | | | | 7)NOTE : NEED TO SUBMIT TWO SETS OF | | | PLANS. | | | | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW . IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|