| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-REAR ELEVATION EXCEEDS THE MAXIMUM |
| | PERCENTAGE OF OPENINGS ALLOWED. TABLE |
| | 600 SBC 1997. REVISE AS REQUIRED. |
| | 2-PROVIDE COMPLETE FRAMING DETAILS FOR |
| | BAY WINDOWS. SPECIFY ALL CONNECTORS AND |
| | FRAMING MEMBERS.SEC. 104.2.2 CITY AMEND |
| | 3-PROVIDE PRODUCT APPROVALS FOR: ROOF |
| | TILE, OVAL WINDOWS, ENTRY DOORS, FIXED |
| | WINDOW ABOVE ENTRY DOORS. |
| | 4-PROVIDE CEILING FANS AS REQUIRED FOR |
| | CREDIT TAKEN IN ENERGY CALCULATIONS. |
| | 5-SPECIFY FOOTING FOR BEARING WALL |
| | BETWEEN GARAGE AND LAUNDRY AREA. |
| | SEC. 104.2.2 CITY AMENDMENTS. |
| | * WHAT IS THE WIDTH OF FOOTING A? |
| | * SPECIFY SIZE AND REINFORCEMENT OF |
| | CONCRETE EDGE AT REAR PORCH SLAB. |
| | 6-SPECIFY LOCATION AND DRAFSTOPPING |
| | MATERIAL AT SECOND FLOOR. SEC. 2305.2 |
| | 7-PROVIDE COMPLETE DETAILS/SECTIONS THRU |
| | STAIRS. SPECIFY ALL FRAMING MEMBERS. |
| | SEC. SEC. 104.2.2 CITY AMENDMENTS. |
| | * SPECIFY THE RISER/TREAD RATIO. SEC. |
| | 1007.3 SBC 1997. |
| | * PROVIDE FIREBLOCKING. SEC. 2304.1 SBC |
| | 8-COMPLETELY SPECIFY THE CEILING |
| | CONSTRUCTION AT FRONT AND REAR PORCHES |
| | AS PER SEC.2504.2 SBC 1997 AND ASTM |
| | C926 AND ASTM C1063. |
| | 9-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | 10-PROVIDE COMPLETE SPECIFICATIONS AND |
| | MOUNTING DETAILS FOR AHU'S. SPECIFY |
| | ALL FASTENERS. SEC. 104.2.2 CITY AMENDM |
| | 11-PROVIDE COMPLETE SPECIFICATIONS AND |
| | SECTIONS/DETAILS FOR BUTT GLAZING AS |
| | PER SECTIONS 2405.3 AND 2406 SBC 1997. |