Plan Review Notes
Plan Review Notes For Permit 99070990
Permit Number 99070990
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00REVISION DATED 07-19-2000 PLUMBING
 (1) NOT APPROVED,DOES NOT SHOW AS BUILT.
 (2) EACH BUILDING HAS A SEPERATE SANITAR
 SEWER LATERIAL.
 (3) GAS PIPING IS INSTALLED UNDER THE
 BUILDING,NOT ABOVE CEILING AS PLANS
 SHOW.
 (3) SHT P2.03 LAW ENFORCEMENT BUILDING,
 RM #137 MOP SINK LOCATION ?
 (4) MAIN WATER SUPPLY, SHOW WHERE PIPE
 SIZES CHANGE.
 (5) WATER HEATERS TO BE READLY ACCESSIBL
 SPC 94 SEC 501.7, IF LOCATED ABOVE 1ST
 FLOOR, A FIXED SHIPS LADDER WITH A
 WORKING PLATFORM IS REQUIRED.
 END OF COMMENTS