Plan Review Notes
Plan Review Notes For Permit 99070990
Permit Number 99070990
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00NUMBER OF REQD.SANITARY FACILITIES SHALL
 COMPLY W/SPC TABLE 407.
  
 CAPACITY OF LP TANK,TYPE OF PIPING,AND
 SOURCES OF IGNITION IN PROXIMITY TO LP
 TANK SHALL BE SHOWN ON THE PLANS PER
 NFPA 58.
  
 SANITARY SYSTEM FOR ADMIN.BLDG.TO COMPLY
 W/COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.911.1.1.(ONLY FIXTURE DRAINS
 PERMITTED ON WET VENTS.)
  
 CLARIFY SIZE OF BLDG.SEWER.(CIVILS SHOW
 6" AND PLBG.DWGS.SHOW 4".)