| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD OF EACH BUILDING |
| | TO ENSURE COMPLIANCE W/TABLE 407 FOR |
| | MINIMUM PLBG.FIXTURE REQ'S. |
| | |
| | CAPACITY AND E.F RATING OF WATER HEATERS |
| | ARE REQ'D.PER FLA.ENERGY CODE SEC.103.2 |
| | |
| | FLOOR DRAINS ARE REQ'D. IN THE TOILET |
| | ROOMS PER SPC SEC.409.4.1.1. |
| | |
| | WALLS IN TOILET ROOMS SHALL COMPLY W/ |
| | SBC SEC.1204.2 |
| | |
| | KITCHEN /BREAKROOM SINKS IN EACH |
| | BUILDING SHALL COMPLY W/F.A.C.B.C.SEC. |
| | 4.24.1-4.24.7. |
| | |
| | DRINKING FOUNTAINS ARE REQ'D.IN EACH |
| | BUILDING PER SPC TABLE 407. |
| | |
| | SHT.A5.04-CLEARLY SHOW ALL MOUNTING |
| | HEIGHT DIMENSIONS FOR HANDICAP FIXTURES. |
| | COMPLY W/F.A.C.B.C. |
| | |
| | SHOWER DIMENSIONS SHALL COMPLY W/ |
| | F.A.C.B.C.SEC.4.21.2. |
| | |
| | CONTROLS IN HANDICAP SHOWERS SHALL |
| | COMPLY W/F.A.C.B.C.SEC.4.21.5. |
| | |
| | CIVIL DRAWINGS NOTE SANITARY SEWER AS 6" |
| | AND SHT.P2.01 NOTES 8".CLARIFY. |
| | |
| | FALL OF BUILDING DRAIN/SEWER SHALL |
| | COMPLY W/TABLE 714.1(MIN.SLOPE IS 1/8" |
| | PER FT.SEE SHT.P2.01.) |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | 610.4.1, 610.4.2. |
| | |
| | MAX.TEMP.OF WATER TO RESTROOMS SHALL |
| | NOT EXCEED 110 DEGREES F.PER F.E.C. SEC. |
| | 412.1ABCD.2.3.2. |
| | |
| | |
| | |
| | |
| | |
| | SUBMIT COMPLETE GAS DRAWING FOR REVIEW. |
| | INDICATE TYPE OF PIPING,BTU LOAD, |
| | LOCATION AND CAPACITY OF LP TANK, |
| | SOURCES OF IGNITION IN PROXIMITY TO TANK |
| | COMPLY W/STD.GAS CODE SEC.104.2.1,NFPA |
| | 58. |
| | |
| | AN INTERCEPTOR SHALL BE INSTALLED ON THE |
| | DISCHARGE LINE FROM THE INDUSTRIAL DRAIN |
| | BY THE MAINTENANCE FACILITY PER SPC SEC. |
| | 1004.1.CLARIFY NATURE OF EFFLUENT AND |
| | OPERATIONS PERFORMED IN THIS AREA.SPC |
| | 104.2.1. |
| | |
| | SIZE THE WATER RISERS IN THEIR ENTIRETY. |
| | SPC 104.2.1. (MAX.OF 2 FIXTURES ON 1/2" |
| | C.W.& 4 FIXTURES ON 1/2" H.W.PER COUNTY- |
| | WIDE AMENDMENTS SEC.607.7. |
| | |
| | SIZE ALL SECTIONS SANITARY RISERS.SPC |
| | SEC.104.2.1. |
| | |
| | DRINKING FOUNTAIN IN ADMIN.BLDG. NOT |
| | PROPERLY VENTED.SPC SEC.901.2.SHT.P4.01 |
| | |
| | SANITARY FOR FISH AND GAME BLDG.DOESN'T |
| | CONNECT TO DRAINAGE SYSTEM.SPC 104.2.1. |