Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CORRECTED BY REVISION
 1) SHOW TERMINATION OF FUME HOOD EXHAUST
 2) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 3) FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED WITH NOTIFICATION BY BLDG. FIRE
 ALARM SYSTEM
 4) BATHROOM EXHAUST TERMINATION TO BE
 MINIMUM 10' FROM WINDOWS, DOORS, AND OUT
 SIDE AIR INTAKE. PROVIDE DETAILS FOR OUT
 SIDE AIR INTAKE AND EXHAUST FAN TERMINA-
 TION